Air - Humidity Measurement from Dry and Wet Bulb Temperature

Estimate air humidity by measuring dry bulb temperature and wet bulb temperature. Use lookup tables to determine relative humidity from temperature difference and dry bulb temperature.

Overview

Air humidity can be estimated by measuring:

  • Dry Bulb Temperature (Tdb) - measured with a simple thermometer
  • Wet Bulb Temperature (Twb) - measured with a thermometer wrapped in wet cloth with continuous air flow

The relative humidity is determined by the difference between these temperatures and the dry bulb temperature value.

Calculator

Inputs

Results

Temperature Difference (Tdb - Twb)-- °
Estimated Relative Humidity-- %
Tdb - Twb (°C)15°C18°C20°C22°C25°C27°C30°C33°C
19091919292929393
28082838485858687
37173757677787980
46265676870717374
55357596164656769
64449525457596163
73642454751535558
82834384145475053
92127313439414548
101320252833364043
Tdb - Twb (°F)60°F64°F68°F72°F76°F80°F84°F88°F
19495959596969696
29090909191929292
38485858687888889
47880818283848485
57375767879808081
66870727375767778
76366676971727374
85861636567687071
95457596163656668
104952555759616365