Air Duct Components - Minor Dynamic Loss Coefficients

Calculate minor or dynamic pressure losses in air duct systems caused by changes in air direction, restrictions, or velocity changes. Uses the formula: Δp_minor_loss = ξ ρ v² / 2

Component or FittingMinor Loss Coefficient (ξ)
90° bend, sharp1.3
90° bend, with vanes0.7
90° bend, rounded radius/diameter duct <10.5
90° bend, rounded radius/diameter duct >10.25
45° bend, sharp0.5
45° bend, rounded radius/diameter duct <10.2
45° bend, rounded radius/diameter duct >10.05
T, flow to branch (applied to velocity in branch)0.3
Flow from duct to room1
Flow from room to duct0.35
Reduction, tapered0
Enlargement, abruptvariable
Enlargement, tapered angle < 8°variable
Enlargement, tapered angle > 8°variable
Grilles, 0.7 ratio free area to total surface3
Grilles, 0.6 ratio free area to total surface4
Grilles, 0.5 ratio free area to total surface6
Grilles, 0.4 ratio free area to total surface10
Grilles, 0.3 ratio free area to total surface20
Grilles, 0.2 ratio free area to total surface50
Calculator

Inputs

Results

Minor Pressure Loss (Δp)-- Pa