Calculate and lookup American Wire Gauge (AWG) specifications including diameter, cross-sectional area, resistance, and current ratings for copper and aluminum conductors. The higher the gauge number, the thinner the wire. This tool provides comprehensive data for single core and multicore wiring cables up to 1000V with PVC insulation at ambient temperatures up to 30°C.

Calculator

Inputs

Results

Diameter-- mm
Diameter-- in
Cross-Sectional Area-- mm²
Electrical Resistance-- Ω/1000m
Maximum Current Rating-- amps
Temperature Correction Factor--
Corrected Current Rating-- amps
AWGDiameter (mm)Diameter (in)Area (mm²)Resistance Cu (Ω/1000m)Resistance Al (Ω/1000m)Current Rating Cu (amps)
400.080.00310.00534485300-
390.090.00350.006426934141-
380.10.0040.007822103397-
370.110.00450.009518102789-
360.130.0050.01313262038-
350.140.00560.01511201767-
340.160.00630.028621325-
330.180.00710.0266631019-
320.20.0080.031556855-
300.250.010.049352541-
280.330.0130.08216331-
270.360.0140.096180276-
260.410.0160.13133204-
250.450.0180.16108166-
240.510.020.2881333.5
220.640.0250.3352805
200.810.0320.534536
1810.040.8221329.5
161.30.0511.3132015
141.60.0642.18.21324
122.10.0813.35.2834
102.60.15.33.3552
83.30.138.32.13.275
64.10.1713.31.3295
45.20.221.20.811.3120
26.50.2633.60.510.79170
17.40.2942.40.410.63180
0 (1/0)8.30.3353.50.320.5200
00 (2/0)9.30.3767.40.260.39225
000 (3/0)10.40.41850.20.32275
0000 (4/0)11.70.461070.160.25325
250--127--345
300--152--390
400--178--415