Boiler - Exhaust Velocity

Recommended boiler exhaust velocities for various boiler configurations and burner types.

Boiler - Exhaust Velocity

This tool provides recommended exhaust velocities for different boiler configurations and burner types.

Boiler Configuration Reference

ConfigurationVelocity (m/s)Velocity (ft/s)Notes
Ducts at minimum load< 4.0< 13Prevent excessive drafting
Stack at minimum load< 5.0< 16Minimum load conditions
One-step burner (on - off)5.0 - 8.016 - 26Basic burner control
Two-step burner (high - low)10 - 1531 - 49Improved modulation
Modulating burner15 - 2549 - 82Full modulation capability
Soot prevention3.0 - 4.09.8 - 13Keep surface free from soot
Calculator

Inputs

Results

Minimum Recommended Velocity-- m/s
Maximum Recommended Velocity-- m/s
Minimum Recommended Velocity (Imperial)-- ft/s
Maximum Recommended Velocity (Imperial)-- ft/s
Boiler ConfigurationMin Velocity (m/s)Max Velocity (m/s)Min Velocity (ft/s)Max Velocity (ft/s)
Ducts at minimum load0 (no limit)< 4.00 (no limit)< 13
Stack at minimum load0 (no limit)< 5.00 (no limit)< 16
One-step burner (on - off)5.08.01626
Two-step burner (high - low)10153149
Modulating burner15254982
Soot prevention (minimum)3.04.09.813