Boiler Blowdown

Calculator and reference guide for boiler blowdown water quality requirements based on ASME guidelines. Calculates electrical conductivity from TDS and compares against maximum allowable impurities for different boiler pressure ranges. Includes water quality references and guidelines for maintaining proper dissolved solids levels to prevent scale formation, carryover, corrosion, and embrittlement.

Calculator

Inputs

Results

Electrical Conductivity-- μS/cm
Boiler Pressure (psig)Iron (ppm)Copper (ppm)Hardness CaCO₃ (ppm)Silica (ppm)Alkalinity CaCO₃ (ppm)TDS (ppm)Conductivity (μS/cm)
0 - 3000.10.050.315070035007000
300 - 4500.050.0250.39060030006000
450 - 6000.030.020.24050025005000
600 - 7500.0250.020.23040010004000
750 - 9000.020.0150.1203007503000
900 - 10000.020.0150.0582006252000

Water Quality Reference Standards

Electrical Conductivity Ranges

Water TypeConductivity (μS/cm)
Ultrapure water (20°C)0.042
Deionized water0.5 - 5
Soft ground water100 - 300
Sea water45,000 - 55,000
Concentrated acids/lyes> 100,000

Key Blowdown Principles

  • Short, frequent blowdowns are more effective at removing boiler water sludge than infrequent long blowdowns
  • Manual blowdown required at boiler bottom to remove settled solids
  • Automatic continuous blowdown uses calibrated valve near water surface for predetermined rates
  • Blowdown tanks required by UPC/UMC codes for installations exceeding 15 psig
  • Recommended maximum TDS levels typically 2,000 - 10,000 ppm depending on boiler type

Problems from Inadequate Blowdown

  • Scale formation
  • Carryover
  • Corrosion
  • Embrittlement

Safety Warning: High pressure and temperature generate large amounts of flash steam during blowdown. Hot water and steam are dangerous—proper design, construction, and operational care required.