Boiler Blowdown Rate
Calculate boiler blowdown rate based on steam consumption, feed water TDS concentration, and maximum allowable TDS in boiler water.
Boiler Blowdown Rate Calculator
A blowdown of the boiler is a routine operation necessary due to the increased concentration of Total Dissolved Solids (TDS) in the boiler water when producing steam.
The blowdown rate can be calculated using the formula:
qBD = qS × fc / (bc - fc)
Where:
- qBD = blowdown rate (kg/h)
- qS = steam consumption (kg/h)
- fc = Total Dissolved Solids (TDS) in the feed water (ppm)
- bc = maximum allowable Total Dissolved Solids (TDS) in the boiler water (ppm)