Chimney's Size vs. Boiler Power

The size of chimney vs. boiler's heat load. Reference table showing required chimney cross-sectional area based on boiler heat capacity.

Boiler Capacity (kW)Boiler Capacity (Btu/h)Required Chimney Area (cm²)Required Chimney Area (in²)
155100011518
237800015023
3511900020031
4615700025039
5819800030047
7023900035054
8127600040062
9331700045070
10435500050078
11639600055085

Conversion Factor

1 kW = 3412 Btu/h

Important Note

⚠️ Always check local authorities before final design.

Usage

Select the boiler capacity closest to your requirements and reference the corresponding required chimney area in both metric (cm²) and imperial (in²) units.