Condensate Generated in Cold Steam Pipes - SI Units

Calculate condensate generation in cold steam pipes when heating up. Estimates the load of warm-up condensate generated when a steam system is heated up based on steam pressure and nominal pipe dimension.

Steam Pressure (bar)50 mm65 mm80 mm100 mm125 mm150 mm200 mm250 mm300 mm350 mm400 mm450 mm500 mm600 mm
09.214.41927374771101134159208262308309
0.351015.920.829405269112146174227287338470
0.711.317.823.433455888125165196255322379529
112.219.525.436506496135179212277350412575
2.513.421.327.8395370105148195232303383450627
415.825.233476382123175233276360454535745
5.517.82837527192138196260308402507598832
719.330.6405777100151214284335438553651906
8.520.131.8425980104157223293349455574676942
1020.833.1436283108162230305361472595700997
1222.635.84767901171762503313925136467601059
1424.238.25071961251892673534185466898111130
1628.14558831131462193124124896388059471320
20365574108150205312463637764981122815031700
253959801171622223385026928281065136216312315
3041.564851241732373605347358821134142017632464
4044.368911321842533855707849401210151418522627