Condensate Generated in Cold Steam Pipes - Sizing of Steam Traps

When cold steam pipes are heated up they generate huge amounts of condensate that must be drained away from the pipe through steam traps. This tool provides a datatable to estimate the warm-up condensate load generated when the steam system is heated up, based on steam pressure and pipe size in Imperial Units (70°F ambient).

Steam Gauge Pressure (psi)2 inch2.5 inch3 inch4 inch5 inch6 inch8 inch10 inch12 inch
06.29.712.818.224.631.9486890
56.91114.420.427.735.95377101
107.511.815.52229.938.85883109
208.413.417.524.933.8446693124
409.915.820.629.339.75278110145
601117.522.932.6445786122162
80121924.935.3486293132175
10012.820.326.937.85167100142188
12513.721.728.4405571107152200
15014.52330435875113160212
17515.324.231.7456179119169224
2001625.333.1476483125177234
25017.227.335.8516989134191252
3002538.35175104143217322443
40027.8435783116159241358493
50030.2466291126173262389535
60032.7506798136187284421579
800385877113203274455670943
10004564861262273055087481052
12005272961402533405668331172
140062791061552803766269221297
160071871171713094156210181432
1750789412618433344874610981544
1800809712918934145976411251584