Condensate Pipe Lines - Sizing

Flow and pressure loss in condensate return lines - SI Units. Determine condensate flow rates and pressure losses for various pipe sizes and pressure drops.

Pressure Loss (Pa/m)Pressure Loss (mbar/m)15mm (1/2")20mm (3/4")25mm (1")32mm (1 1/4")40mm (1 1/2")50mm (2")65mm (2 1/2")80mm (3")
280.28902093808651320255451948079
290.29922144008781340259052718196
300.3932184038901361263153488314
330.33972264149301420274455798677
390.3910724946910281565302561429526
400.410825347610401583306262149639
430.43113263496107916463180645410024
450.45116270508110716873261661810297
470.47119277521113417283338677710523
500.5123286538117217873447694910859
530.53127296557121118463565723511249
550.55130302569123818873638738011476
570.57133308580126119233710752511703
590.59135314591128819593783766611884
610.61138320602131119963851780612111
640.64141327615133820413933797012383
670.67146337634137921004051821012746
690.69148343645140221364119834212973
710.71150348655142421684182847313154
730.73152354665144722004246860013336
760.76155359675146522364305872313563
770.77157365685148822684368885013744
780.78158366689149722824390890013812
800.8160370695151023004427897213925
820.82162375704152923314491907214407
880.88168391733159024274536945314651
900.9170395740160624494717954814787
980.981794147771696256749441002515513
10011804187851701259049901011515649
1141.141944508451832279053661084116828
1181.181984578571860283054431102217055
1201.21994628671880286055021111317282
1311.312094849071969299457611165718053
1371.372154979312018307159061194818507
1401.42165029392037310359651206618688
1471.472245169662096318961281238319187
1571.5723153410022168329863371281419822
1601.623454110112195334064091297320049
1631.6323754610252218337064771310920276
1761.7624657010662309351167401360821092
1801.824957610752331354768081374421319
1961.9626160311292440371071301437922317
200226561111432472376072211456022589
2122.1227362911792549387474301501423270
2162.1627563411882567390574931513223451
2202.227864112002595394275701527723678
2292.2928465512252649402877291560424177
2352.3528866412432689408678431584024522
2402.429267212562719412979271601724780
2452.4529567912702749417380101619325039
2552.5530169412972806426081761652025556
2602.630470113112834430482601668325814
2612.6130570313152844431882871673825900
2742.7431372113482917433185011717326554
2772.7731572713562935445985551728226717
2802.831773013632948447985931735726839
2942.9432574914023025459588131778127533
300332875714143055464189001795627803
3103.133577114383112472690631828028305
3143.1433677514463129475290741838028459
3203.234078414623163482592041857928767
3273.2734479214793198485392991877929076
3333.3334880114953230490494081897929366
3403.435180915113263495595161917829656
3423.4235381315203279498095711927829801
3533.5335882515413328505497071955030237
3593.5936283415563361510397981973230527
3603.636383515583365510998091975430564
3723.7236985015853423520199792009431108
3763.76371854159234385225100242018531253
3803.8373859160134575254100812029931423
3923.92379873162835155339102512063931933
4004383883164635545398103422086632274
4084.08388892166535925457104332109232614
4124.12390896167236085479104782117432750
4204.2394906169036465536105922137833090
4254.25396912170136705570106602150033294

Design Notes

  • Maximum Condensate Flow: Achieved during plant start-up when pipes and equipment are heated up
  • Design Rule: The condensate load used to design condensate pipe lines should be twice the maximum production load
  • Units: SI Units (Pa/m, kg/h)

Equipment Piping and Condensate Load

Typical maximum condensate load and equipment outlet pipe size:

Maximum Condensate Load (kg/h)Outlet Pipe Size (mm, in)
20015 (1/2)
50020 (3/4)
100025 (1)
200032 (1 1/4)
300040 (1 1/2)
500050 (2)
> 500065 - 100 (2 1/2 - 4)