Copper Tubes - Heat Losses

Heat loss from uninsulated copper tubes vs. temperature differences between tube and air.

Nominal Bore (mm)Nominal Bore (inches)22°C ΔT (W/m)38°C ΔT (W/m)55°C ΔT (W/m)40°F ΔT (Btu/hr ft)68°F ΔT (Btu/hr ft)99°F ΔT (Btu/hr ft)
151/2213245223447
223/4284360294553
281345376365679
351 1/4416489436793
421 1/247741044977108
54259931316297136
672 1/27111115674116162
7638312918187135189
1084107165232111172241

Notes

  • 1 W = 3.4 Btu/hr
  • 1 ft (foot) = 0.3048 m

Reference

Heat loss values from uninsulated copper pipes vary based on the nominal bore diameter and the temperature difference between the tube and the surrounding air. Use the table above to determine heat losses for your specific application.