Electric Motors - 230 & 460V Three Phase Circuits Wiring
Sizing of copper wire and transformers for three phase 230 & 460V electrical motors. This tool provides wire gauge recommendations based on motor horsepower, voltage, apparent power, and distance from motor to transformer.
Notes
- All wiring and electrical connections should comply with the National Electrical Code (NEC) and with local codes and practices.
- Apparent Power: The power supplied to the electric circuit - typical from a power supplier to the grid - to cover the real and reactive power consumption in the loads.
- For rows marked 'See note': The local power company should be consulted.
- If undersized wire is used between the motor and the power source, the starting and load carrying capabilities of the motor will be limited.
Conversion Factors
- 1 hp = 0.746 kW
- 1 ft (foot) = 0.3048 m
Wire Gauge (AWG) Reference
The table above provides recommended copper wire gauges (American Wire Gauge) based on motor horsepower, operating voltage (230V or 460V three-phase), apparent power in kVA, and distance from motor to transformer in feet. Lower AWG numbers indicate larger diameter wires.