Electric Motors - 230 & 460V Three Phase Circuits Wiring

Sizing of copper wire and transformers for three phase 230 & 460V electrical motors. This tool provides wire gauge recommendations based on motor horsepower, voltage, apparent power, and distance from motor to transformer.

Transformer (HP)Voltage (V)Apparent Power (kVA)100 ft150 ft200 ft300 ft500 ft
1.523031212121210
246031212121212
32303121212108
246031212121212
3230512101086
346051212121210
52307.5108864
54607.5121212108
7.52301086642
7.546010121212108
102301564441
1046015121212108
152302044420
154602012101086
20230See note42210
20460See note108864
25230See note22200
30230See note21100
30460See note86642
40230See note10000
50230See note10000
50460See note44220
60460See note42200
75230See note00000
75460See note42200

Notes

  • All wiring and electrical connections should comply with the National Electrical Code (NEC) and with local codes and practices.
  • Apparent Power: The power supplied to the electric circuit - typical from a power supplier to the grid - to cover the real and reactive power consumption in the loads.
  • For rows marked 'See note': The local power company should be consulted.
  • If undersized wire is used between the motor and the power source, the starting and load carrying capabilities of the motor will be limited.

Conversion Factors

  • 1 hp = 0.746 kW
  • 1 ft (foot) = 0.3048 m

Wire Gauge (AWG) Reference

The table above provides recommended copper wire gauges (American Wire Gauge) based on motor horsepower, operating voltage (230V or 460V three-phase), apparent power in kVA, and distance from motor to transformer in feet. Lower AWG numbers indicate larger diameter wires.