EN 1057 Copper Tubes - Dimensions Calculator

Calculator for EN 1057 Copper and copper alloys - Seamless, round copper tubes for water and gas in sanitary and heating applications. Calculate inner diameter and cross-sectional area based on nominal outside diameter and wall thickness.

Calculator

Inputs

Results

Inner Diameter-- mm
Cross-Sectional Area-- mm²
Tube Designation Example--
Material TemperCommonly Used TermSize Range (mm)Tensile Strength (MPa)Elongation min. (%)Vickers Hardness (HV5)
R220Annealed, soft6 - 542204040 - 70
R250Half hard6 - 66.72502075 - 100
R290Hard6 - 159290595 - 120
Nominal Outside Diameter (mm)Tube Length (m)Wall Thickness Option 1 (mm)Wall Thickness Option 2 (mm)
63, 60.60.8
83, 60.60.8
103, 60.60.8
153, 60.71.0
223, 60.91.2
283, 60.91.2
353, 61.21.5
423, 61.21.5
543, 61.22.0
673, 61.22.0
763, 61.52.0
1083, 61.52.5
1333, 61.5
1593, 62.0
21963.0

EN 1173 - Letter Symbols for Property Designations

  • A: Elongation
  • B: Spring bending limit
  • G: Grain size
  • H: Hardness (Brinell for castings, Vickers for wrought products)
  • M: (as) Manufactured, i.e. without specified mechanical properties
  • R: Tensile strength (like R220 - 220 MPa)
  • Y: 0.2% proof strength

Example - Designation

Copper tube EN 1057 R250 12×1.0

Where R250 is the material temper designation.

Conversion

1 inch = 25.4 mm