Epoxy Pipes - Support Spacing

Support spacing for reinforced Epoxy fiberglass pipes. Maximum distance between epoxy fiberglass pipe supports at different operating temperatures. Maximum operating temperature for epoxy pipes should not exceed 300 °F (149 °C).

Nominal Pipe Size (inches)Nominal Pipe Size (mm)75 °C / 24 °F - Spacing (m)75 °C / 24 °F - Spacing (ft)150 °C / 66 °F - Spacing (m)150 °C / 66 °F - Spacing (ft)175 °C / 79 °F - Spacing (m)175 °C / 79 °F - Spacing (ft)200 °C / 93 °F - Spacing (m)200 °C / 93 °F - Spacing (ft)225 °C / 107 °F - Spacing (m)225 °C / 107 °F - Spacing (ft)250 °C / 121 °F - Spacing (m)250 °C / 121 °F - Spacing (ft)
1253.29.939.839.72.99.42.89.32.78.7
1 1/2403.511.63.511.43.411.33.4113.310.83.110.1
250413.13.912.93.912.83.812.43.712.23.511.4
3804.6154.514.84.514.64.314.24.314413
41005.116.7516.5516.34.815.84.815.64.414.5
61505.818.95.718.65.618.45.517.95.417.6516.4
82006.1206.120619.85.919.35.8195.417.7
102506.1206.1206.1206.1206.1205.718.8
123006.1206.1206.1206.1206.120619.7
143506.1206.1206.1206.1206.1206.120