Insulated Copper Tubes - Heat Loss

Heat loss to surrounding air from insulated copper tubes. The heat loss is based on temperature difference 55°C (99°F) with insulation thickness 25 mm (1 inch) and conductivity coefficient k = 0.043 W/m°C (0.3 Btu in/ft²hr°F).

Nominal Bore (mm)Nominal Bore (inches)Heat Loss (W/m)Heat Loss (Btu/hr ft)
223/488
2811010
421 1/211.512
54214.515
672 1/21617
7631920

Conversion Factors

  • 1 W = 3.4 Btu/hr
  • 1 ft (foot) = 0.3048 m

Parameters

  • Temperature Difference: 55°C (99°F)
  • Insulation Thickness: 25 mm (1 inch)
  • Conductivity Coefficient (k): 0.043 W/m°C (0.3 Btu in/ft²hr°F)