Oil Fuels - Viscosities vs. Temperatures
Viscosities of fuel oils vs. temperature. Saybolt Universal Seconds (SSU) - kinematic viscosity versus temperature for typical fuel oils.
Key Information
- Temperature Conversion: TF = TC × 9/5 + 32
- Viscosity Conversion: SSU (Saybolt Universal Seconds) ≈ centiStokes (cSt) × 4.55
- Note: This equation is approximate and valid only for a specific range of viscosities. For more accurate conversions, refer to ASTM D2161.
- Pumping Limit: 4 - 5000 SSU is the maximum practical limit for pumping
- Atomization Range: 150 - 300 SSU for fuel oil no. 5 and 6
References
- Kinematic Viscosity vs. Dynamic Viscosity
- Viscosity Converter Chart
- ASTM D2161: Standard Practice for Conversion of Kinematic Viscosity to Saybolt Universal Viscosity