Pipes and Cylinders - Conductive Heat Loss

Calculate conductive heat loss through uninsulated or insulated pipes and cylinders using thermal conductivity and temperature differences.

Pipes and Cylinders - Conductive Heat Loss

Calculate conductive heat loss through the wall of uninsulated or insulated cylinders and pipes.

Uninsulated Cylinder or Pipe

Q = 2π L (tᵢ - tₒ) / (ln(rₒ / rᵢ) / k)

Insulated Cylinder or Pipe

Q = 2π L (tᵢ - tₒ) / ((ln(rₒ / rᵢ) / k) + (ln(rₛ / rₒ) / kₛ))

Insulated Cylinder or Pipe with Convective Heat Resistance

Q = 2π L (tᵢ - tₒ) / (1 / (hc rᵢ) + (ln(rₒ / rᵢ) / k) + (ln(rₛ / rₒ) / kₛ))

Calculator

Inputs

Results

Calculator

Inputs

Results

Heat Transfer (Q) - Uninsulated-- W
Calculator

Inputs

Results

Heat Transfer (Q) - Insulated-- W
Calculator

Inputs

Results

Heat Transfer (Q) - Insulated with Convective Resistance-- W