Relief Valves - Length of Vent Pipes

Calculate length of safety valves vent pipes. Determines the maximum length of relief valve vent lines based on relief pressure, inside diameter, and air flow.

Calculator

Inputs

Results

Maximum Length of Vent Line (lm)-- feet
Relief Pressure (psi)Inside Diameter (inches)Air Flow (lbs./min)Maximum Length (feet)
250.5500.89
25110014.22
251.515080.37
500.5752.16
50115034.56
501.5225195.52
1000.7510029.88
1001.25200234.38
1001.5250336.67
Relief Valves - Length of Vent Pipes | MEPKit Engineering Tools | MEPKit