Hazard ClassificationCeiling and Sidewall ConstructionMaximum Protected Area (ft²)Maximum Protected Area (m²)
LightStandard pendent and upright sprinklers - Unobstructed22520.9
LightNon combustible obstructed22520.9
LightCombustible obstructed16815.6
LightStandard sidewall sprinklers - Combustible finish12011.1
LightStandard sidewall sprinklers - Noncombustible finish19618.2
OrdinaryStandard pendent and upright sprinklers - All13012.1
OrdinaryStandard sidewall sprinklers - Combustible finish807.4
OrdinaryStandard sidewall sprinklers - Noncombustible or limited combustible finish1009.3
ExtraStandard pendent and upright sprinklers - All1009.3
High-piledStandard pendent and upright sprinklers - All1009.3