Water Supply Lines - Sizing

Sizing water supply service and distribution lines based on Water Supply Fixture Units (WSFU). Select supply pressure range and pipe configuration to determine maximum WSFU capacity for various pipe lengths.

Calculator

Inputs

Results

Maximum Water Supply Fixture Units (WSFU)-- WSFU
Pressure Range--
Meter Service Line (in)Building Supply Line (in)40 ft60 ft80 ft100 ft150 ft200 ft
3/41/2654321
3/43/416141296
13/42523211715
11363127252017
1 1/41544742383228
Meter Service Line (in)Building Supply Line (in)40 ft60 ft80 ft100 ft150 ft200 ft
3/41/2776543
3/43/4202019171411
13/4393936332823
11393939363025
1 1/41787876675244
Meter Service Line (in)Building Supply Line (in)40 ft60 ft80 ft100 ft150 ft200 ft
3/41/2777654
3/43/4202020201713
13/4393939393530
11393939393932
1 1/41787878787462
Water Supply Lines - Sizing | MEPKit Engineering Tools | MEPKit